Augier's transformer substations are modularly designed units that guarantee performance. They are available in step-up or step-down models for indoor or outdoor use.
-
Most popular related searches
Benefits
Made from sheets of painted aluminium, RAL 1015, IP44, bottom-less station, front closed by a door with a three-point handle.
- Waterproof transformer
IP68, from 3kVA to 63kVA
- Adjustment taps +- 5%
- Equipped on the 950V side with a three-position load break switch,
allowing the mains to disconnected and grounded.
- For use with single-phase or three-phase networks
- Network fuse protection 950V, fuses incorporated in the transformer
Specification
- Power rating (kVA) 3 to 32 kVA
- Step-up transformer : primary voltage 230 V or 400 V
- Step-up transformer : no load secondary voltage 970 V
- Step-down transformer : primary voltage 950 V
- Step-down transformer : no load secondary voltage 235 V or 410 V
- Insulation class primary / secondary 1100 V
Features
Waterproof transformer from 3 kVA to 63 kVA
- Coupling
Single-phase or three-phase
- Dimensions Small model XS
Lenght (mm) + LV compartment (mm) 750 + 300
Depth (mm) 600
Height (mm) 1020
Average weight without transformer (kg) 65 - Transformer
watertight IP68
- Dimensions Large model XL
Lenght (mm) + LV compartment (mm) 1205 + 300
Depth (mm) 845
Height (mm) 1520
Average weight without transformer (kg) 1110
Optional Functions
- Mechanical
Substation with bottom and anti-insect grill on the vents
Ronis lock to secure isolating switch
Low-voltage compartment equipped according to needs - Protection
Unbalanced current protection achieved by differential torus and associated double-threshold relay
Isolating controller, P1 card and cardew (for neutral IT mode)
Thermal protection at one temperature threshold, contact output on terminals
Surge arrester on 950 V side but also, if applicable, on low-voltage side - Additional features
Supplemental 950 V load break switch (XL version only)
“In service” position for terminal output switch
Doubling of the 950 V terminals to allow passage through the artery
Heat resistant and thermostat