Chillers System
After H2S removal the gas is fully saturated with water; the relative humidity (RH) is 100%. If water droplets should reach the cylinder heads and combustion chambers the water will destroy the oil film. This will lead to increased wear of moving parts as well as substantial reduction of the lifetime of the engine oil. Therefore, it is necessary to dry the gas to avoid condensation in the pipe system and the engine’s gas train and intercooler.
-
Most popular related searches
How it Works
The cleaned gas is cooled from typically 40°C or 55°C - depending on whether the anaerobic digester is mesophilic or thermophilic - down to 15°C. After cooling the relative humidity is still 100% but the gas contains 10 g water/kg gas only at 15°C compared to 50 g at 400C and 115 g at 55°C. When the gas is compressed in the gas booster the temperature is raised to 30-35°C and the relative humidity reduced to 30-40% before the gas train.
Simple and Robust Design
The system comprises two circuits; i.e. the Gas Chiller cooling the gas by scrubbing it with chilled gas condensate and the Water Chiller that supplies cold water for the process. Each system is designed for the project specific flow and temperature conditions.
Process Description
- The hot and moist biogas enters the Gas Chiller in the bottom.
- In the cooling zone, the gas is in direct contact with chilled gas condensate and the temperature and dew point drops.
- In the demister zone droplets are removed before the gas leaves from the top of the Gas Chiller to protect downstream equipment.
- In the heat exchanger the gas condensate is chilled with water from the Water Chiller.
- The auto-drain ensures that excess gas condensate is automatically drained from the Gas Chiller.