Siemens Oxymat - Model 61 - Continuous Oxygen Gas Analyzers
From Continuous Gas Analytics - Oxymat 6/61/64
For oxygen standard applications. The OXYMAT 61 is a cost-effective oxygen analyzer for standard applications. The OXYMAT 61 requires ambient air as reference gas. This is supplied by a pump that is integrated into the analyzer housing. Alternatively, pressurized bottle air can be used. The OXYMAT 61 measures oxygen using the paramagnetic alternating pressure method. This guarantees perfect linearity and allows parameterization of small measuring ranges (0 to 2%) up to 0 to 100% in a single device. The SIL 2 classification obtained by OXYMAT 61 makes it easier for plant operators to comply with the statutory requirements regarding proof of risk reduction.
-
Most popular related searches
Technical Specifications
- Max. number of components: 1
- Components: Oxygen
- Minimal measuring range: 0-2 %
- Housing: 19' rack
Benefits at a Glance
- Integrated pump for reference gas delivery (optionally for ambient air, for example)
- High degree of linearity
- Compact design
- Physically suppressed zero point possible
Design
- 19' rack unit with 4 HU for installation
- in hinged frame
- in cabinets with or without telescope rails
- Front plate can be swung down for servicing purposes (laptop connection)
- Gas connections for sample gas inlet and outlet; pipe diameter 6 mm or ¼'
- Gas and electrical connections at the rear
Display and control panel
- Large LCD field for simultaneous display of:
- Measured value
- Status bar
- Measuring ranges
- Contrast of LCD panel adjustable using menu
- Permanent LED backlighting
- Washable membrane keyboard with five softkeys
- Menu-driven operation for parameterization, test functions, adjustment
- User help in plain text
- Graphic display of concentration trend; programmable time intervals
- Bilingual operating software German/English, English/Spanish, French/English, Spanish/English, Italian/English
Input and outputs
- One analog output per medium (from 0, 2, 4 to 20 mA; NAMUR parameterizable)
- Six binary inputs freely configurable (e.g. for measurement range switchover, processing of external signals from sample preparation)
- Six relay outputs freely configurable (failure, maintenance request, maintenance switch, threshold alarm, external magnetic valves)
- Two analog inputs configurable (e.g. correction of cross-interference, external pressure sensor)
- Extension with eight additional binary inputs and eight additional relay outputs, e.g. for autocalibration with up to four calibration gases
Communication
RS 485 present in basic unit (connection from the rear).
Options
- RS 485/RS 232 converter
- RS 485/Ethernet converter
- RS 485/USB converter
- Connection to networks via PROFIBUS DP/PA interface
- SIPROM GA software as service and maintenance tool
Application
Application areas
- Environmental protection
- Boiler control in firing systems
- Quality monitoring (e.g. in ultra-pure gases)
- Process exhaust monitoring
- Process optimization
Further applications
- Chemical plants
- Gas manufacturers
- Research and development
Customer reviews
No reviews were found for Siemens Oxymat - Model 61 - Continuous Oxygen Gas Analyzers. Be the first to review!