The Cadillac BTU Meter (HEATX) is designed to measure the energy consumed in hot water heating and chilled water cooling systems. The system is a rate and totalizing device, which is capable of calculating and displaying Volume, Energy, Temperatures and Peak Energy usage. Combined with Cadillac’s superior flow meter technologies the HEATX provides the most accurate, repeatable, and maintenance free energy system available in the industry.
Product Details
The Cadillac BTU Meter (HEATX) measures the temperature in the feed and return lines via two precision matched 4-wire RTD’s and from this calculates the density and enthalpy of the water. In addition, by also measuring the volume of water flowing in the system via the Cadillac flow meter, the HEATX will then compute, display, and output the Energy consumed.
The New Industry Standard
Combined with Cadillac’s superior flow meter technologies the HEATX BTU meter has quickly become acknowledged as the industry standard. Customers choose the Cadillac HEATX BTU Meter because of proven: accuracy, dependability, consistency, maintenance, reliability and rangeability.
Cadillac BTU / Energy Meter has the ability to provide the best suited and widest range of application solutions to meet the end users energy measurement needs.
Applications & Features
Cadillac® HEATX BTU Meter - Applications
The Cadillac® HEATX BTU / Energy Meter is the meter of choice for energy applications. This BTU meter can be applied effectively for the following purposes:
- Energy consumption data source for energy management system, DCS, district-wide systems.
- Energy-Customer Billing from accurately totalized Energy / BTU meter measurements.
- Basis for internal cost distribution using campus-wide systems.
- Efficiency measuring and monitoring from central control rooms.
- Direct Energy / BTU meter measurements at both Boiler and point of use locations.
Cadillac® HEATX BTU Meter - Features
The Cadillac® HEATX BTU Meter is the meter of choice for energy applications. This meter contains the following features:
- Heating Mode: Where Positive ΔT's only are totalized.
- Cooling Mode: Where Negative ΔT's only are totalized.
- Heating/Cooling Mode: Where the flow of energy may be for either heating or cooling. In this mode the energy total is increased regardless of whether the ΔT is positive or negative.
- Charge/Discharge Mode: Where two separate registers totalize positive and negative totals.
Operation Principles
The Cadillac® HEATX BTU Meter measures the temperature in the feed and return lines via two precision matched 4-wire RTD's and from this calculates the density and enthalpy of the water. In addition, by also measuring the volume of water flowing in the system via the Cadillac® flow meter, the HEATX BTU meter will then compute, display, and output the Energy consumed.
Power is Calculated:
- P = V x p x (htv-htr)
Where:
- P = Power (watts)
- V = Volumetric flow Rate
- p = Density
- htv = Specific enthalpy at Feed temperature
- htr = Specific enthalpy at Return temperature