SAE-IT - Model net-line FW-5-GATE - Micro-Telecontrol Station
From Telecontrol & Substation Automation
In order to offer more communication possibilities in an even smaller space, integrated inputs/outputs have been omitted. The FW-5-GATE can of course also be supplemented with expansion modules and interface modules. It offers cost-effective solutions for intelligent secondary distribution networks and smart metering through further interfaces with SML/SyM² meter integration, among others. An integrated temperature sensor measures the station temperature, which can be used e.g. for overload checks on a transformer.
The FW-5-GATE is equipped with additional interfac...
The FW-5-GATE is equipped with additional interfaces for coupling external components to form intelligent networks. As with all the devices of the series5 series of products, the connection to the control centre can be made by many communication routes and protocols directly or with telecontrol interfaces, backed up with redundant systems if required.
Local meter integration is made via a second LAN connection with SML protocol or via the additional serial interface with IEC 62056-21 protocol. In the CL variant S0 meter pulse detection can also be used.
- Intelligent secondary unit substation with integration of earth fault/short circuit indicators, network analysis systems and protective devices
- Smart meter integration in energy management systems and remote meter reading control centres
- Intelligent measurement point for wide range regulation in distribution networks
- Field device in transformer substations with protection device coupling
- Monitoring of media and infrastructure systems in pipelines
On demand, a FW-5-GATE may be delivered as a plug & play prepared solution. We individually assemble compontens and cabinets on your demand and functionality, ready-made for a quick set-up. Aside the RTU the set regularly consists all required devices such as communication modems, UPS, relay, terminals and so on. The devices are usually mounted in cabinets from Rittal or Eaton.
Technical Data
Capacity and Functionality
The basic system can be expanded according to individual requirements and has impressive dielectric strength:
- 2 Ethernet LAN TCP/IP connections
- 2 RS-485 field interfaces
- CL/S0 meter interface in FW-5-GATE-cl
- RS-232/V.24 interface
- Temperature sensor, -20° to 100° C
- Integrated wide range power supply unit, 20 to 72 V DC
- or 230 V AC power supply in FW-5-GATE-230
- IEC 62056-21 meter connection (IEC 1107)
- SML SyM² meter connection via Ethernet
- DSFG interface for natural gas equipment
- Modbus RTU/TCP master/slave
- MPI/3964R/RK512 field bus
- NTP/SNTP/DCF clock synchronisation
Supported Protocols
- IEC 61850 IED and protective device coupling
- IEC 60870-5-101 telecontrol technology, station control technology
- IEC 60870-5-103 protective device coupling
- IEC 60870-5-104 TCP/IP coupling to control centre
- DNP3 server, serial/IP
Communication Paths
- dedicated lines
- PSTN dial-up lines
- radioLAN
- TETRA-radio
- FO, fibre optics
- DSL and SHDSL
- 3G/4G mobile communication via GPRS, EDGE, HSPA/UMTS and LTE
Customer reviews