Small Turbo Generator PD Sensors
From Turbo-Generator Assessment
Typically used for motors and small turbo generators (less than 100 MVA), Bus couplers detect stator winding PD activity and help separate unwanted electrical noise. In the recent years, Epoxy Mica Capacitors (EMCs) became the industry's choice due to sufficient sensitivity and the relative ease of installation. The number and type of couplers required depends on the application and type of machine. Three couplers are typically needed for motors, whereas 6 couplers are typically used on generators. A standard package includes 3 to 6 couplers, mounting hardware, insulating tapes, termination box, and coaxial cables. A typical installation takes 1.5 to 2 days for a set of 3 couplers, and up to 4 days for a set of 6 couplers.