Smart Energy Manager for coolcept, coolcept-x, coolcept³, coolcept³-x, StecaGrid 8000+ 3ph and 10000+ 3ph. The feed-in management solution: The StecaGrid SEM offers different options of realising feed-in management with a photovoltaic system. A ripple control receiver from the relevant distribution grid operator can be connected. The feed output at the grid connection point can be limited to an adjustable value, or the ripple control signal can be switched to the relay output. Up to ten inverters can be connected to the StecaGrid SEM via the RS 485 interface.
-
Most popular related searches
Easiest installation
Easiest installation
StecaGrid SEM can be installed in the switching cabinet right next to the ripple control receiver. The casing features a dimensioning typical for switching cabinets and can be mounted onto a top-hat rail. Direct power supply at 230 V. A mains adapter plug or an external direct current power supply are not required.
All connected StecaGrid inverters can be accessed via a USB interface on the StecaGrid SEM. Connection to a PC is possible via a standard USB cable. The interface is on the front side of the casing – the cover does not need to be removed in the switching cabinet.
Features
Product features
- Wall-mounting with top-hat rail
- Compact and robust product design
- Quiet and emission-free
- Maintenance-free
- Firmware update possible
Displays
- 4 LEDs show operating states
Interfaces
- Steca RS-485 bus
Options
- Can be connected to a data logger
Certificates
- Compliant with European Standards (CE)
- Made in Germany
Technical Data
- Characterisation of the operating performance
- Own consumption: < 3 W
- Operating conditions
- Area of application: indoor rooms with or without air conditioning
- Interface to inverter: Steca RS-485 bus with max. 1,000 m cable length and 10 bus participants at maximum
- Ambient temperature: 0 °C … +60 °C
- Storage temperature: -40 °C … +85 °C
- Relative humidity: 0 % … 95 %
- Noise emission: silent
- Fitting and construction
- Degree of protection: IP 20
- Terminal (fine / single wire): 1.5 mm² / 2.5 mm²
- Dimensions (X x Y x Z): 72 x 91 x 58 mm
- Weight: 300 g
- Power supply: 230 V / 50 Hz or 60 Hz
- Communication interface: 2 x RJ45; 4 x analogue for ripple control receiver, via screw-type terminals; USB, type B socket; S0 interface
- Relay output: potential-free contact, 250 V AC / 16 A
- Test certificate: see certificate download on the product page