WattNode - Energy and Power Meter
The WattNode® Module for Modbus® is a kilowatt hour (kWh) energy and power meter with ANSI C12.1 and ANSI C12.20 class 0.5 accuracy. Designed for easy customization for nearly any application or type of equipment, the WattNode Meter Module provides bidirectional energy and power readings via an RS-485 port using Modbus RTU communications. One model can measure all 1, 2, or 3 phases, in delta or wye services, from 120 to 600 Vac, with a single model. Using external current transformers, it can measure 5 to 6,000 amps. The WattNode Module is instrument powered from 6-24 Vdc or from an isolated 12-24 Vac control transformer. It is packaged in a compact, DIN-rail mount enclosure.
-
Most popular related searches
Measurements
- Supports floating-point and integer registers
- Active (real) power: watts, individual meter elements and sum of elements
- Reactive power: VARs, individual meter elements and sum of elements
- Power factor: individual meter elements and sum of elements
- Active (real) energy: kilowatt-hours (kWh), individual meter elements and sum of elements; net, positive, and negative
- Reactive energy: kVAR-hours, individual meter elements and sum of elements; net, positive, and negative
- AC line frequency (Hz)
- RMS voltage line-to-neutral: VAN, VBN, VCN
- RMS voltage line-to-line: VAB, VBC, VCA
- RMS current: CT1, CT2, CT3
- Demand: individual meter elements and sum of elements
- Peak demand sum: minimum and maximum
- Apparent power demand
Specification
Accuracy
The following accuracy specifications do not include errors caused by the current transformer accuracy or phase angle errors. “Rated current” is the current that generates a CT output voltage of 0.33333 Vac or equivalent milliamp output.
Unless otherwise noted, all accuracy specifications assume the following conditions:
- Line voltage: 100 to 690 Vac
- Power factor (PF): 0
- Frequency: 48 – 62 Hz
- Ambient Temperature: 23°C ± 5°C
- CT Current: 1% – 100% of rated current
Revenue Models
- Meet the ANSI C12.1-2008 standard for revenue metering when used with class 0.6 or better current transformers.
- Meet the ANSI C12.20-2010 standard for revenue metering when used with class 0.3 or better current transformers.
Measurement
- Update Rate: 0.1 second. Internally, all measurements are performed at this rate, except the energy registers, which are updated every 1.0 second.
- Start-Up Time: Energy measurement starts ~100 milliseconds after the supply voltage is applied. Modbus communication is enabled ~300 milliseconds after the supply is applied; at this time, all the registers will report valid data, such as power, voltage, current, etc.
- Default CT Phase Angle Correction: 0.0 degrees.
ElectricalPower Supply
- Nominal Power Supply Voltage: 6 to 24 Vdc or isolated 12 to 24 Vac source
- Power Supply Minimum Operating Voltage: 6 Vdc or 10 Vac
- Power Supply Absolute Maximum Voltage: 40 Vdc or 30 Vac
- Power Supply Watts: typical 0.6 W, maximum 1.0 W
- Power Supply Current (milliamps):
General Electrical
- Line Frequency: 45 to 65 Hz
- Nominal Line-to-Neutral Vac: 90 to 347 Vac
- Nominal Line-to-Line Vac: 120 to 600 Vac
- Measurement Over-Voltage Limit: 720 Vac
- Over-Current Limit: 200% of rated current. Exceeding 200% of rated current will not harm the meter, but the current and power will not be measured accurately.
- Maximum Surge: EN 61000-4-5: 2kV, ANSI C12.1 combination wave: 6kV, 1.2/50 μs – 8/20 μs
- Line Voltage Power Consumption: The line voltage sensing circuitry draws 0.006 watts per phase at 120 Vac, increasing to 0.150 watts per phase at 600 Vac.
- Real Power (50-60 Hz):
- Power Factor: ~1.0
- Rated VA: 25 VA at 720 Vac, 50 Hz. The Rated VA is the maximum at 115% of nominal Vac at 50 Hz.
- Measurement Category: The line voltage measurement terminals on the meter are rated for CAT III, 600 Vac. Measurement Category III is for measurements performed in the building installation. Examples are measurements on distribution boards, circuit-breakers, wiring, including cables, bus-bars, junction boxes, switches, plug loads, and equipment for industrial use and some other equipment, for example, stationary motors with a permanent connection to the fixed installation.
Current Transformer Inputs:
- Voltage Mode:
- Nominal Input Voltage (At CT Rated Current): 0.33333 Vac RMS
- Absolute Maximum Input Voltage: 5.0 Vac RMS
- Input Impedance at 50-60 Hz: 23 kΩ
- Current Mode:
- Nominal Input Current (At CT Rated Current): 40 mA RMS
- Absolute Maximum Input Current: 200 mA RMS
- Input Impedance at 50-60 Hz: 10 Ω
EIA RS-485 Interface
- RS-485 Output Isolation: 4500 Vac RMS
- Driver Output:
- Voltage (Open Circuit): ±6 Vdc maximum
- Voltage (54 Ω load): ±1.5 Vdc minimum
- Current (54 Ω load): ±60 mA typical
- Rise Time (54 Ω || 50 pF load): 900 nS typical
- Receiver:
- Common-Mode Range: -7 Vdc to +12 Vdc max
- Sensitivity: ±200 mV
- Bus Load: 1/8 unit load (up to 64 meters)
- Failsafe Modes: bus open, shorted, and idle
Regulatory
- UL: UL Listed 2808
- UL / IEC 61010-1, 3rd Edition
- CAN/CSA-C22.2 No. 61010-1-12, 3rd Edition
- FCC: Class B, FCC Part 15, radiated and conducted emissions
- CE: EN 61326-1: 2013, industrial locations
- Radiated Emissions: CISPR / EN 55011, Class B
- Conducted Emissions: CISPR / EN 55011, Class B
- Electrostatic Discharge: EN/IEC 61000-4-2: (B) Self-Recovering
- Radiated RF Immunity: EN/IEC 61000-4-3: (A) No Degradation
- Electrical Fast Transient / Burst: EN/IEC 61000-4-4: (A) No Degradation
- Surge Immunity: EN/IEC 61000-4-5: (A) No Degradation
- Conducted RF Immunity: EN/IEC 61000-4-6: (A) No Degradation
- Power Frequency H-field Immunity: EN/IEC 61000-4-8: (A) No Degradation
- Voltage Dips, Interrupts: EN/IEC 61000-4-11: (B) Self-Recovering
- RoHS Compliant
Environmental
- Operating Temperature: –40°F to 176°F (–40°C to +80°C)
- Operating Humidity: non-condensing, 5 to 90% relative humidity (RH) up to 104°F (40°C), decreasing linearly to 50% RH at 131°F (55°C)
- Operating Altitude: Up to 9842 ft (3000 m)
- Pollution: POLLUTION DEGREE 2 – Normally only non-conductive pollution; occasionally, a temporary conductivity caused by condensation must be expected
- Indoor Use: Suitable for indoor use
- Outdoor Use: Suitable for outdoor use if mounted inside an electrical enclosure (Hammond Mfg., Type EJ Series) rated NEMA 3R or 4 (IP 66)
Mechanical
- Enclosure: High impact, ABS/PC plastic
- Flame Resistance Rating: UL 94V-0, IEC FV-0
- Size: 19 in. × 3.68 in. × 1.15 in. (106.4 mm × 93.4 mm × 29.1 mm)
- Connectors: Euroblock pluggable terminal blocks
- Green: up to 12 AWG (2.5 mm2), 600 V
- Black: up to 12 AWG (2.5 mm2), 300 V
- Weight: 4.7 oz (134 gm)
Features:
- Meets ANSI C12.1 and ANSI C12.20 Class 0.5 revenue metering standards
- Small form factor for easy installation inside most electrical panels, see a sample
- installation diagram
- Pluggable screw terminals for easy wiring
- 0.5% accuracy nominal (see manual for details)
- True RMS power even with leading or lagging power factor and chopped or distorted waveforms
- Measure variable speed drive pumps and motors
- Safe CT’s (Current Transformers), output 0.333 Vac at rated current.
- Split core CTs for quick installation
- Solid core CTs are less expensive and prevent tampering
- CTBL large split-core CTs for high currents (standard and custom sizes)
- CTRC Rogowski Coils for tight spaces where rigid CTs do not fit
- UL, cUL Listed – Designed and tested for safety and use throughout North America.
- Assembled in USA, qualified under the Buy American provision in the American Recovery and Reinvestment Act of 2009 (ARRA).
- Five year warranty
- Compact, DIN-rail mount design
- Instrument powered from 6-24 Vdc or a isolated 12-24 Vac source