High Voltage, Inc.

HVIModel ALT-130/60 and ALT-130/60F -AC High Voltage Aerial Lift Dielectric Test Set

SHARE

The ALT Series, including models ALT-130/60 and ALT-130/60F, are field portable AC hipot test sets developed to evaluate the dielectric strength of aerial lifts, booms, bucket trucks, and liners in accordance with ANSI 92.2 standards. These units feature a continuously adjustable AC voltage, a versatile voltmeter with two ranges, a multi-range current meter, and an integrated timer. The test sets are adept at performing pass/fail over-voltage withstand tests on capacitive loads such as switchgear and substation apparatus. Utilizing a gapped core transformer, they deliver up to 7.2 kVA of output power, with a 3.6 kVA draw, allowing operation from either 30A, 120Vac or 15A, 230Vac inputs. For applications requiring different power levels, the PFT Series and ABT Series accommodate lower power needs, while the FPA, HPA, and PAR lines serve higher power demands.

Most popular related searches

The ALT-130/60 and ALT-130/60F from our ALT Series of field portable AC hipot test sets are primarily designed for testing the dielectric strength of aerial lifts, booms, bucket trucks and liners per the ANSI 92.2 standard. With a continuously adjustable AC voltage, 2 range voltmeter, multi range current meter and built in timer, the ALT Series are also a great choice for a pass/fail, AC over-voltage withstand testing on larger capacitive loads such as switchgear, buss duct or other substation apparatus. A gapped core transformer for up to 7.2 kVA of output power with the draw of 3.6 kVA so the hipot can be powered by a 30A, 120Vac or 15A, 230Vac input. For lower power requirements please see our PFT Series and ABT Series. For higher power requirements see our FPA, HPA and PAR lines.

  • Secondary connected 2 Range Voltmeter: 0-30/60kV & 0-60/130kV
  • 2 Range Current Meter: 0-250uA and 0-1.0mA with x1, x10, x100 multipliers
  • Full 7.2 kVA, 60kV tap for bucket liner testing
  • Fixed overload set to 120% of variable transformer rated output current
  • Transit protected meters prevent meter damage between test sites
  • Guard/Ground circuit for accurate leakage current measurement
  • Gapped core transformer design for capacitive load compensation
  • Zero Start and External safety Interlock provisions
  • Input: (ALT-130/60) 120 V, 60 Hz, 30 A
  • (ALT-130/60F) 230 V, 50/60 Hz, 15 A
  • Output: 0-130kV AC / 0-60 kV AC, 3.6 kVA resistive load
  • Up to 7.2KVA capacitive load (1.3 nF @ 130kV or 5.3nF @
  • 60kV, 60 Hz) Output current is reduced at lower voltages
  • Duty: 7.2 kVA: 1 hour ON, 2 hour OFF
  • 4 kVA: continuous
  • Voltmeter: 3.5”, scaled 0-30/60kV & 0-60/130kV kV AC, ±2% F.S.
  • Current Meter: 3.5”, scaled 0-250uA and 0-1.0mA ±2% F.S. with rangemultipliers of x1, x10, x100
  • Distortion: Less than 5%
  • Size and Weight: (W x D x H) Case:
  • 21 x 11.25 x 15.25 in., 46 lb.
  • 534 x 286 x 387 mm, 21 kgHV Tank:
  • 15.5 x 15.5 x 27.5 in., 160 lb.
  • 394 x 394 x 699 mm, 73 kg
  • Output Termination Top toroid (0-130 kV)
  • 1 inch ball side tap (0-60 kV)
  • Scope of Supply 20ft black ground lead, 20ft shielded return cable, external interlock plug, handtruck, operations manual, calibration certificate