- Home
- Companies
- Meier Energy
- Products
- VARSine ActivSine - Active Harmonic ...
VARSine ActivSine - Active Harmonic Filter
The ActivSine series active harmonic filter is a comprehensive power quality solution designed to enhance electrical efficiency and reliability. It employs a three-level neutral point clamped (NPC) topology circuit, which features 12 IGBT power devices per phase, enabling the generation of three distinct voltage levels at the output. This architecture not only improves voltage quality and lowers harmonic distortion but also minimizes the need for additional output filters, thereby reducing associated costs. The filter is engineered in various configurations, including wall-mounted, rack-mountable, and cabinet versions, each supporting different amperage ranges from 30A up to 600A. Its modular nature allows users to scale their systems by paralleled connection of up to 20 modules, providing higher current capacities for varying applications. Capable of real-time automatic power factor correction and load balancing, the ActivSine series is a versatile tool in the modern electrical landscape, making it suitable for industrial, commercial, and utility-scale deployments.
The ActivSine series active harmonic filter operates on a three-level topology circuit. It provides power quality solutions such as harmonic elimination, real-time automatic power factor correction, and load balancing. It is available in three versions: a wall-mounted enclosure version, ranging from 30A to 150A, a rack-mountable version for standard 19” cabinets, ranging from 30A to 150A, and a cabinet version, ranging from 100A to 600A.
Its modular design allows users to easily achieve the desired filter current capacity by connecting up to 20 modules in parallel.
- Network voltage range : -20%~+20% : -20%~+20% : -20%~+10%
- Nominal current (A) : 30-50-75-100-150-200 : 100-200-300-400-500-600 : 100-200-300-400-500-600
- Frequency : 50/60Hz (-10%~+10%)
- Harmonic compensation : from the 2nd to the 50th harmonic order
- Harmonic compensation rate : >97%.
- CT Configuration in loop : Closed or open (open loop is recommended for parallel operation)
- Overall response time : 10ms
- Network type : 3P3W, 3P4W
- Overload capacity : 110% – Continuous operation, 120% – 1 min
- Circuit topology : 3-level topology
- Switching frequency : 20 kHz – Reaction time: approximately 50 ps
- Modules : Up to 20 units can be combined
- Redundancy configuration : Master/Master or Master/Slave
- Typical power losses : 2.5% (depending on load)
- Reactive power compensation : Available
- Target power factor : Adjustable from -1 to 1
- Load balancing : Available (for three-phase networks with neutral 3P4W)
- Display : HMI 1.8/4.3/7 inches
- Communication ports : RS485 Modbus (RTU)
- Noise level : <69 dB (en fonction de la charge et du modèle){{{wpml_tag_142}}} {{{wpml_tag_143}}} {{{wpml_tag_144}}} {{{wpml_tag_145}}}Utilisation en altitude{{{wpml_tag_146}}} {{{wpml_tag_147}}}>2000m
- Temperature : Operating temperature: -35°C to 55°C, reduced use above 55°C
- Storage temperature: -45°C to 70°C
- Humidity : 5%~95% RH, Noncondensing
- Protection class : IP20
- Design/Approvals : EN 62477-1(2012), EN 61439-1 (2011)
- EMC : EN/IEC 61000-6-4, Classe A
- Certification : CE, Cmim