OVERALL SIZE
- 240 mm x 181 mm x 42 mm (9.4” x 6.8” x 1.6”)
PANEL CUTOUT SIZE
- 220 mm x 160 mm (8.7" x 6.3")
MAXIMUM PANEL THICKNESS
- 8.0 mm (0.3”)
WEIGHT
- 0.86kg
PRODUCT VARIANTS
- 7310-01 - 7310 Auto Start Control Module
- 7310-02 - 7310 Auto Start Control Module (Htr)
- Heated display option
- 3-phase generator sensing
- Power monitoring (kW h, kV Ar. kV Ah, kV Ar h).
- Remote communications {RS232 8 RS4S5)
- Configurable inputs/outputs [9`8).
- CAN and magnetic pick-up sensing
- Fuel usage monitor and low level alarms.
- Tier 4 CAN engine support.
- True dual mutual standby with load balancing timer.
- Configurable display languages.
- Power save mode.
- Integral PLC editor.
- Flexible sender inputs.
- DSE Configuration Suite PC Software
- Configurable event log {250).
- Load switching, load shedding & dummy load outputs.
- Ensures the display continues to operate in extreme cold weather conditions.
- Provides true generator sensing.
- Provides dear accurate power measurement information
- Provides secure and simple off site monitoring. All ports are continuously active.
- Provides multiple installation options.
- Makes the module ideal for standard and electronic engine applications.
- Tracks the amount of fuel being used and sounds an alarm if over/under fuel use is detected.
- Ensures the control module can be used with the latest in modern electronic engine technology.
- Enables two set systems to be configured to allow for redundancy or balancing run hours.
- Ensures the control module is suitable for worldwide use.
- Reduces the power usage within system batteries.
- Ensures additional applications are easily integrated into the system.
- Allows alternative sender types to be selected using one input.
- Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
- Provides access to historical alarms and operational status.
- Allows load options and dummy load requirements to be independently controlled.
DC SUPPLYCONTINUOUS VOLTAGE RATING
- 8 V to 35 V Continuous
- Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
- LEDs and backlight will not be maintained during cranking.
- 340 mA at 12 V, 160 mA at 24 V
- 160 mA at 12 V, 80 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
- 0 V to 35 V OUTPUTS
OUTPUT A (FUEL)
- 15 A DC at supply voltage
OUTPUT B (START)
- 15 A DC at supply voltage
OUTPUTS C & D
- 8 A 250 V (Volt free)
AUXILIARY OUTPUTS E,F,G,H
- 2 A DC at supply voltageGENERATOR
VOLTAGE RANGE
- 15 V to 415 V AC (Ph to N)
- 26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
- 3.5 Hz to 75 Hz
- MAGNETIC PICK-UP
VOLTAGE RANGE
- +/- 0.5 V to 70 V
FREQUENCY RANGE
- 10,000 Hz (max)
ELECTRO-MAGNETIC COMPATIBILITY
- BS EN 61000-6-2
- EMC Generic Immunity Standard for the Industrial Environment.
- BS EN 61000-6-4
- EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
- BS EN 60950
- Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
- BS EN 60068-2-1
- Ab/Ae Cold Test -30°C.
- BS EN 60068-2-2
- Bb/Be Dry Heat +70°C.
VIBRATION
- BS EN 60068-2-6
- Ten sweeps in each of three major axes.
- 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
- BS EN 60068-2-30
- Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
- BS EN 60068-2-78
- Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
- BS EN 60068-2-27
- Three shocks in each of three major axes 15 gn in 11 ms.
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
- BS EN 60529
- IP65 - Front of module when installed into the control panel with the optional sealing gasket.