Deep Sea Electronics Ltd (DSE)
  1. Companies
  2. Products
  3. CHESTGRAPH - Model HI-101 - Portable ...

Model DSE7310 MKII - Auto Start Control Module

SHARE

The DSE7310is a feature packed Auto Start Control Module designed to control single diesel or gas gen-set applications.

Most popular related searches

OVERALL SIZE

  • 240 mm x 181 mm x 42 mm (9.4” x 6.8” x 1.6”) 

PANEL CUTOUT SIZE

  • 220 mm x 160 mm (8.7" x 6.3")

MAXIMUM PANEL THICKNESS

  • 8.0 mm (0.3”)

WEIGHT

  • 0.86kg

PRODUCT VARIANTS

  • 7310-01 - 7310 Auto Start Control Module
  • 7310-02 - 7310 Auto Start Control Module (Htr)
  • Heated display option
  • 3-phase generator sensing
  • Power monitoring (kW h, kV Ar. kV Ah, kV Ar h).
  • Remote communications {RS232 8 RS4S5)
  • Configurable inputs/outputs [9`8).
  • CAN and magnetic pick-up sensing
  • Fuel usage monitor and low level alarms.
  • Tier 4 CAN engine support.
  • True dual mutual standby with load balancing timer.
  • Configurable display languages.
  • Power save mode.
  • Integral PLC editor.
  • Flexible sender inputs.
  • DSE Configuration Suite PC Software
  • Configurable event log {250).
  • Load switching, load shedding & dummy load outputs.
  • Ensures the display continues to operate in extreme cold weather conditions.
  • Provides true generator sensing.
  • Provides dear accurate power measurement information
  • Provides secure and simple off site monitoring. All ports are continuously active.
  • Provides multiple installation options.
  • Makes the module ideal for standard and electronic engine applications.
  • Tracks the amount of fuel being used and sounds an alarm if over/under fuel use is detected.
  • Ensures the control module can be used with the latest in modern electronic engine technology.
  • Enables two set systems to be configured to allow for redundancy or balancing run hours.
  • Ensures the control module is suitable for worldwide use.
  • Reduces the power usage within system batteries.
  • Ensures additional applications are easily integrated into the system.
  • Allows alternative sender types to be selected using one input.
  • Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
  • Provides access to historical alarms and operational status.
  • Allows load options and dummy load requirements to be independently controlled.
DC SUPPLYCONTINUOUS VOLTAGE RATING
  • 8 V to 35 V Continuous
CRANKING DROPOUTS
  • Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. 
  • LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
  • 340 mA at 12 V, 160 mA at 24 V
MAXIMUM STANDBY CURRENT
  • 160 mA at 12 V, 80 mA at 24 V

CHARGE FAIL/EXCITATION RANGE

  • 0 V to 35 V OUTPUTS

OUTPUT A (FUEL)

  • 15 A DC at supply voltage

OUTPUT B (START)

  • 15 A DC at supply voltage

OUTPUTS C & D

  • 8 A 250 V (Volt free)

AUXILIARY OUTPUTS E,F,G,H

  • 2 A DC at supply voltageGENERATOR

VOLTAGE RANGE

  • 15 V to 415 V AC (Ph to N)
  • 26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE

  • 3.5 Hz to 75 Hz
  • MAGNETIC PICK-UP

VOLTAGE RANGE

  • +/- 0.5 V to 70 V

FREQUENCY RANGE

  • 10,000 Hz (max)

ELECTRO-MAGNETIC  COMPATIBILITY

  • BS EN 61000-6-2
  • EMC Generic Immunity Standard for the Industrial Environment.
  • BS EN 61000-6-4
  • EMC Generic Emission Standard for the Industrial Environment.

ELECTRICAL SAFETY

  • BS EN 60950
  • Safety of Information Technology Equipment, including Electrical Business Equipment.

TEMPERATURE

  • BS EN 60068-2-1
  • Ab/Ae Cold Test -30°C.
  • BS EN 60068-2-2
  • Bb/Be Dry Heat +70°C.

VIBRATION

  • BS EN 60068-2-6
  • Ten sweeps in each of three major axes.
  • 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.

HUMIDITY

  • BS EN 60068-2-30
  • Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
  • BS EN 60068-2-78
  • Cab Damp Heat Static 40° C @ 93% RH 48 Hours.

SHOCK

  • BS EN 60068-2-27
  • Three shocks in each of three major axes 15 gn in 11 ms.

DEGREES OF PROTECTION PROVIDED BY ENCLOSURES

  • BS EN 60529
  • IP65 - Front of module when installed into the control panel with the optional sealing gasket.