Chongqing Gold Mechanical & Electrical Equipment Co.,Ltd

Gold - Model GDBC-901 - Automatic Transformer Turns Ratio Tester
The voltage ratio measurement for three or singe phase transformer. The group vector measurement for three phase transformer. The polarity measurement for single phase transformer or CT/PT. Voltage ratio error calculation. Current transformer ratio measurement. Excitation current measurement in ratio testing. Reproduction the AC test voltage from power source to reduce the effects of bad power source. Save the test results in the memory internal the tester. Print the test results by micro printer. Reverse connection detect unit to prevent the high voltage injected to operator. Over current protection unit integrated in software and hardware. Upload the test results to PC by RS232 and make word report by software.
Most popular related searches
three-phase transformer
transformer testing
current transformer
high voltage operations
AC power source
power testing
power test
- Ratio measurement range:1—10000
- Group measurement:1—12
- Phase measurement error:1 degree
- Ratio measurement error:1—2000 ± 0.2%RDG 2000—10000 ± 0.5%RDG
- Test voltage:0~80V, frequency 50Hz
- Power supply:AC220V ± 10%, 50Hz/60Hz
- Environment temperature: 0-50°C
- Humidity: ≤85%RH
- Size 400mm´350mm´200 mm
- Weight:7kg