Eagle Eye Power Solutions, LLC

Eagle Eye PowerEyeModel BMS - Battery Monitoring Systems for UPS Applications

SHARE

When it comes to power outages, little can be more costly to data centers than unforeseen downtime. According to the Uptime Institute’s most recent report: 54% of data centers reported outage costs over $100,000 USD. 16% of data centers reported outage costs over $1,000,000 USD. In order to avoid costly outages, it’s vital to ensure the health of the backup battery system that is required to perform when power is lost. Be ready for any negative occurrence with 24/7/365 remote battery monitoring and make sure your system is ready to perform as needed when called upon. If not, you run the risk of finding out there is a battery failure after it’s too late and a costly outage is inevitable.

Most popular related searches
  • Battery Voltage
  • Battery Internal Resistance
  • Battery Temperature
  • Battery State of Health
  • String Voltage
  • String Current
  • Ambient Temperature

Equip your team with the timely data it needs to make proactive decisions that will help protect your business.

Key Features
Protect your business, employees, and infrastructure by:
  • Extending the life of your battery system
  • Reducing maintenance and replacement costs through proactive preventative maintenance
  • Providing maximum benefit with minimal labor investment
  • Achieving remote access to manage your business anytime, anywhere
  • Planning battery procurement to avoid emergency situations
  • Verifying warranty status with recorded data and reporting
  • Reducing business insurance premiums by mitigating unnecessary risks
The Eagle Eye PowerEye BMS measures:
  • Battery Voltage
  • Battery Internal Resistance
  • Battery Temperature
  • Battery State of Health
  • String Voltage
  • String Current
  • Ambient Temperature

Control Module

  • Operating Temperature: 0-50°C ( 32-122°F )
  • Storage Temperature: -10-70°C ( 14-158°F)
  • Relative Humidity Ratio: 5% – 90% RH
  • Atmospheric Pressure: 80 – 110 kPa
  • Power Input: 12VDC @1.5A
  • Max. Power Consumption: 20 Watt
  • RS-485: Modbus RTU
  • Ethernet: SNMP, Modbus TCP/IP (optional)
  • Number of String: 4 Strings can be monitored
  • Number of String Unit: 1 String Unit at each String
  • Number of Battery Monitoring Unit: 120 Battery Monitoring Unit at each
  • Battery Support: 1.2V – 12V Batteries
  • String Voltage: 1.2V – 2500VDC
  • Relay Output: 2 x Dry Contact Output, 400V (AC-DC) 120mA (optionally digital)
  • Digital Input: 2 x 12-24VDC
  • Electrical Isolation: 2000 V
  • Dimensions (H x W x D): 40.5 x 200 x 95.5 mm
  • Enclosure: Metal
  • Color: Grey

String Module

  • Current Range: 0-500A
  • Resolution: 10 mA
  • Accuracy: 1%
  • Current Sensor: Hall Effect Sensor
  • Temperature Range: 0-50°C ( 32-122°F )
  • Resolution: 0.1°C
  • Accuracy: ±2 °C
  • Voltage Range: 1-2500 V DC
  • Resolution: 10 mV
  • Accuracy: 0.1%
  • Humidity Range: 5% – 90% RH
  • Resolution: 1% RH
  • Accuracy: 5%
  • Isolation: 2000 V Opto Isolation
  • Short Circuit Protection: Max. 3.5A (Internal Fuse)
  • Operating Temperature: 0-50°C ( 32-122°F )
  • Storage Temperature: -10-70°C ( 14-158°F )
  • Relative Humidity Ratio: 5%-90% RH
  • Atmospheric Pressure: 80-110kPa
  • Power Consumption: 1.2 Watt
  • Nominal Operation: 100 mA
  • Data Transmission Interface: Serial Modbus Protocol
  • Dimensions ( H x W x D ): ( 91 x 63 x 29 mm )
  • Enclosure: ABS
  • Color: Semi-Transparent Grey

Battery Module

  • Battery Type: VRLA, Ni-Cd, VLA
  • Voltage Range: 1-16V
  • Resolution: 1 mV
  • Accuracy: 0.05 % ± 6 mV
  • Resistance Range: 0.1 – 64m ohms
  • Resolution: 1μOhm
  • Accuracy: ±2 %
  • Temperature Range: 0-50°C ( 32-122°F )
  • Resolution: 0.1°C
  • Accuracy: ±2 °C
  • Isolation: 2000 V Opto Isolation
  • Short Circuit Protection: Max. 3.5A (Internal Fuse)
  • Reverse Polarity Protection: Provides protection at rated voltage against reverse connection
  • Operating Temperature: 0-50°C ( 32-122°F )
  • Storage Temperature: -10-70°C ( 14-158°F )
  • Relative Humidity Ratio: 5%-90% RH
  • Atmospheric Pressure: 80-110kPa
  • Power Consumption: 50mA @2V Battery
  • 10mA @12VBattery
  • Nominal Operation: 10mA – 50mA
  • Internal Resistance Measurement During Test: 0.167 A/dk
  • Sleep Mode: >2 mA
  • Data Transmission Interface: Serial Modbus Protocol
  • Auto Addressing: Automatically obtain address during installation or replacement
  • Voltage Balancing: Voltage balancing feature on string
  • Dimensions ( H x W x D ): ( 91 x 63 x 29 mm )
  • Enclosure: ABS
  • Color: Semi-Transparent Grey