CELLTRON™ Ultra - Model FEGRID-0008 -Battery Tester
The CELLTRON™ Ultra provides advanced battery testing capabilities for stationary batteries used in UPS systems, power utility, telecommunications industries and is ideal for use in data centers or other environments with high levels of electrical interference noise.
CRITICAL POWER CONFIDENCE
The CELLTRON™ Ultra combines advanced conductance technology, state-of-the-art portable electronics and convenient data management to facilitate fast, simple, safe and accurate battery management.
STRAIGHTFORWARD FUNCTIONALITY
Tests lead-acid batteries that are 2, 4, 6, 8, 10, 12, 14, and 16 Volt and can test batteries providing power to a load (in service) or not providing power (not in service).
SOLID HARDWARE
Backlit graphical LCD, integrated infrared data transmitter, removable SD card, interchangeable probe and clamp testing interfaces, and a rechargeable on-board battery pack.
HIGH NOISE IMMUNITY
The enhanced conductance testing methodology enables accurate and repeatable testing in the presence of ultra-high electrical interference.
BUILT-IN MULTIMETER
The versatile multi-meter function allows for the measurement of AC & DC voltage and current. Scope mode displays AC ripple current and more.
The CELLTRON™ Ultra software includes an icon-based menu and pre-loaded data on over 200 battery models to expedite testing and record-keeping. Over 250 pre-established reference/benchmark values are stored to assist in the development of battery pass/fail thresholds.
TEST
Measures the status of a jar in voltages and conductance values. It displays conductance values in mhos.
BATTERY SETUP
Configure testing information including site name, test jars only or jars & straps, battery voltage (2 Volt or 16 Volt).
BATTERY MANAGER
Data on 12 battery manufacturers is pre-loaded to expedite testing and record-keeping process.
REPORTS
Print results, transfer to PC, add a Battery, test counter & version.
UTILITIES SETUP
Update warning thresholds, temperature (C or F), mode-to change from automatic to manual test, or update to the latest firmware.
DIGITAL MULTIMETER
Measures AC & DC voltage, Current and Scope mode.
Applications
- Tests individual lead acid cells or monoblocs (up to 16 Volts) in any common configuration, approximately 10-6000 Ah
Test Data Storage
- 500 string locations of 480 test results per string stored internally
User Programmable Functions
- Preset values for over 250 battery types
- Low voltage alarm setting
- Low conductance warning
- Low conductance alarm
- Test mode (pushbutton/auto start)
Calibration
- Franklin Electric Grid Solutions will work with each customer to establish a regular calibration program if it is required by their quality or other management systems
Connectorized Test Cable Options
- Dual contact clamps
- Dual contact probes
- Custom cables by quotation
Power Requirements
- 9.6V, 1600mAH, NiMH
- Internal swappable battery & charger
LCD - FSTN Display
- 2.619 in x 1.309 in
- 128 x 64 pixels
- 40 degree viewing angle
- Contrast ratio 8
- Green LED backlight
Keypad
- Stainless-steel dome
- Polycarbonate overlay
- 1,000,000 actuations
Data Transfer
- Infra-red HP protocol
- Infra-red
- Half-duplex IRDA protocol
- RS-232 printer
- Secure digital card
Environmental Operating Range
- 0 to +104°F (0 to +40°C)
- 95% relative humidity
- Non-condensing
Over Voltage Protection
- Auto-reset disconnect
- Reverse polarity protected
Housing Material
- Acid-resistant ABS plastic
- Santoprene™ overmold
Specifications
- Voltage Range : 1.5 - 20.0 Volts DC
- Conductance Range : 100 - 19,990 Siemens
- Accuracy : + 2% across test range
- Voltmeter Resolution : 5mV
- Storage Temperature : -4 to 180°F (-20 to 82°C)
- Analyzer Dimensions : 11in x 4in x 3in (279mm x 105mm x 80mm)
- Analyzer Weight : 2.6 lb (1 Kg)
- Case Dimensions : 19in x 15.5in x 7in (485mm x 395mm x 180mm)
- Shipping Weight : 11 lb (5 Kg)