Continental Refining Company (CRC), LLC
- Home
- Companies
- Continental Refining Company (CRC), LLC
- Products
- CRC UltraBurn - Model F20 - FXX Blend ...
CRC UltraBurn - Model F20 -FXX Blend Petroleum Fuel
If used for tax exempt purposes, fuel required to have enough Solvent Red 164 dye to be visually apparent. Must meet the standard of 3.9 lbs. Solvent Red 26 per thousand barrels product. Dyed Biodiesel contains Solvent Red (ASTM D6258H) minimum 0.1 mg/L and maximum 20 mg/L.
Most popular related searches
biodiesel blend
biodiesel blending
biodiesel
biodiesel generator
fuel testing method
biodiesel testing
fuel monitoring
biodiesel product
fuel testing
biodiesel production
- B6 to B20 Blends will have a range of 1.9-4.1. If Diesel Grade No. 1-D or a mix of Grades No. 1-D and Grade No. 2-D, the minimum viscosity shall be 1.3 mm2/s.
- If Grade No. 1-D or blends of Grade No. 1-D and Grade No. 2-D diesel fuel are used, or a cloud point of less than -12°C is specified, the minimum flash point shall be 38°C.
- The cloud point of biodiesel is generally higher than petroleum based diesel fuel and should be taken into consideration when blending.
- It is not necessary to test biodiesel blends for lubricity, as the ULSD is tested and will only be used if meets specification.
- The electrical conductivity of the fuel oil is measured at the time and temperature of the fuel at delivery.
- Other test methods may be used.
- In house testing capabilities
- Cold Filter Plugging Point (CFPP) – October 1st – April 30th Maximum: -10°F