iVolt integrated LV panel featuring a seamless bypass system this provides total continuity of site supply and through the GPRS modem transmits data on the performance of the iVolt unit. Industry’s first ever fully integrated VO/LV. Integrated switch panel. Fully automatic bypass. Highly innovative seamless change-over.
Most popular related searches
circuit breaker
surge protection
energy building management system
industrial control transformer
voltage optimization
energy management
condenser protection
energy management system
power transformer
- Technology: Microprocessor controlled transformer tap selection using thyristors
- Capacity: 32A to >3000A
- Efficiency: 99.4% at full load
- Response time: 15ms
- Input voltage range: 253/438 volts down to 220/380 volts
- Output voltage range: 220/380 volts, adjustable
- Output accuracy: ± 1.5%
- Phase control: Three phases balanced independently
- Frequency: 47Hz to 75Hz
- Waveform distortion: <0.25%
- Transformer materials: Low loss electrical steel core with high purity copper conductors
- Conductor Insulation class: Class H
- Temperature class: Class B
- Operating temperature: 0 – 55ºC
- Operating humidity: 95% non-condensing
- Ingress protection: IP21
- Overload capacity: 150% for 4 minutes
- Standards: BS EN 61558-1 2005, EN61000-6-4, IEC 61000-4-3, IEC 61000-4-2, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-11
- Expected Service life: >25 years
- Warranty: 15 years (parts and labour) on all transformer windings and electronic control boards
- Circuit breaker(s): Input and/or output circuit breakers
- Manual bypass: External manual bypass including isolation
- Auto bypass: External auto bypass including circuit breaker for isolation
- High level surge protection:
- Class 1 and 2 spike and surge protection
- Protection L – N: 25kA @ 10/350μs
- Protection N – PE: 100kA @ 10/350μs
- Voltage protection level: 1.5kV
- Remote monitoring system: Connection to energy management or building management systems
- Harmonic reduction transformer: Reduced power harmonics from supply and load