These transformers are specifically designed to handle non-linear and non-sinusoidal loads that arise from a variety of power electronic applications. Their usage can be found in configurations that require diode, thyristor, or motor drive options with multiple pulse configurations like 6, 12, 24, 36, 48, or 60. The design incorporates special considerations to manage additional harmonic heating, more severe axial forces, and substantial overloads and short circuit forces compared to standard power transformers. Employing high-grade materials, these transformers offer enhanced performance and reliability, leveraging superior engineering expertise and extensive manufacturing experience.Most popular related searches
Liquid filled Variable Speed Drive Duty Transformers are designed to handle non-linear, non-sinusoidal loads resulting from their use, with a variety of power electronic applications such as diode, thyristor or motor drive configurations from 6, 12, 24, 36, 48, or 60 pulse configurations.
Special design considerations should be used to account for the additional harmonic heating, more severe axial forces, severe overloads and short circuit forces that can be seen as compared with a standard power transformer. Niagara Power Transformer’s superior engineering expertise paired with our unmatched years of manufacturing experience and high-grade materials allow us to provide the best in-class Variable Speed Drive Duty Transformer.
- Specialty circuit configurations
- Multiple phase shifts starting at 12
- Up to 50 MVA base rating
- Up to 138 kV, 650 kV BIL
- Copper or aluminum wound
- Designed to meet specific harmonic spectrums
- Industry leader in process and high current applications
- Seismic classifications
- Mineral Oil, Enviro Temp FR3, Luminol, or other liquids
- Sealed tank or conservator tank designs
- Special dimensional requirements
- Non-standard elevation and ambient designs
- Special service conditions
- Meet Standard C57.18.10
- For variable speed motor drive applications
- Cancel harmonics to the power system