Sunguard
Most popular related searches
- Power Supply : 24VDC
- Rated Current: 2.5A
- Current Range: 0-2.5A
- Power : 60W
- Tolerance: ± 1.0%
- Setup : 100ms, 30ms/230VAC
- Voltage Range: 88 ~ 264VAC 124 ~ 370VDC
- Frequency Range: 47 ~ 63Hz
- efficiency (Typ.) : 84%
- Overload : 105 ~ 160% rated power output
- Protection type: Constant current limiting, recovers automatically after fault condition is removed
- High Voltage : 27.6 ~ 32.4V
- Operating Temperature : -20 ~ +60 °C
- Humidity level of operation : 20 ~ 90% RH non-condensing
- Storage Temperature : -40 ~ +85
- Safety standards : UL60950-1, TUV EN60950-1 approved, Design refer to EN50178
- Withstand voltage : I/P-O/P:3KVAC
- Isolation : I/P-O/P:100M Ohms/500VDC
- EMS immunity : Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
- MTBF : 216.2K hrs min. MIL-HDBK-217F (25°C )
- Dimensions : 78 mm x 93 mm x 56 mm
- Weight : 0.3Kg