Elko Machine Electrical Panel Manufacturing Inc.

ElkoSheet Kiosk Transformer Station

SHARE

ECSS type MV / LV Distribution Transformer Centers are metal enclosed. housing; It is made of 2mm thick galvanized sheet and painted with electrostatic powder paint in desired color. welding is not used in the manufacture of the housing to prevent corrosion. operating type; <> and <> Operated types are available. All casing, metal doors and ventilation panels are electrically connected to each other to provide a equipotential structure.

Most popular related searches

In the compact center;

  • MV Switchgear Section,
  • LV Panel Section,
  • MV / ag Distribution Transformer Section.

  • Rated Voltage (kV): 12; 24; 36
  • Maximum rated power * (kVA): 630; one thousand; 1250
  • Enclosure class: 10; 20
  • Degree of protection of the enclosure (TS EN 3033 EN 60529): IP 23d; IP 43
  • Internal arc resistance: 20 kA-1s
  • Applied standard: TS EN 62271-202

* Maximum Rated Power
indicates the rated power of the largest transformer to be used in the compact center considering the Enclosure Class .