Features; 1 to 3 KVA. Ready to "Plug and Play". Solid State and Economical. EMI Shielded, High Isolation.  Heavy-duty Filters. Voltage Regulation. Output Distribution. 1 Year Factory Warranty.

Most popular related searches
  • Mini Power : 2"H x 6.5"W x 12"D
  • Constant Power 3 : 10.5"H x 11"W x 16"D
  • Sizes : 1, 1.5, 2, 2.5 and 3 KVA (Single Phase)
  • Input Voltage : 120 or 208 or 240 VAC
  • Output Voltage : 120 or 120/240 VAC
  • Frequency : 50 Hz or 60 Hz ±5%
  • Response Time : 1 cycle typical
  • Harmonic Distortion : <1% maximum added
  • Audible Noise : Meets or exceeds NEMA standards
  • Common-Mode : -120 dB (.1 Hz to 10 MHz)
  • Normal-Mode : -60 dB/decade (1KHz to 10 MHz)
  • Overload (Inrush) : 200% of full load for 10 seconds 1000% of full load for 1 cycle
  • Load Rating : Continuous, regardless of load/line conditions
  • Input Volt Regulation Range +7% to -23% of nominal
  • Output Volt Regulation Range : ±5% typ. ±6% All line-load conditions
  • Efficiency : 96% min.
  • CP3 Output Receptacle : 2 optional receptacle positions
  • Load Power Factor : 0.3 leading or lagging to unity
  • Transformer : Single phase, dual-shielded, computer grade, iso-lation
  • transformer, copper wound
  • Operating Temperature : 32°F (0°C) to 104°F (40°C)
  • Storage Temperature : -4°F (-20°C) to 140°F (60°C)
  • Operating Humidity : 10 to 95% non-condensing