LumaSense Technologies, Inc.

- Model 2 - Effective Fiber Optic Hot Spot Monitor and Controller for Power Transformers

From

0

The ThermAsset®2 is a much sought after addition to LumaSense's Luxtron product line, offering a primary controller to monitor hot spots, control cooling, and protection at a cost that is attractive to the apparatus engineers and system operators.

  • Dynamic Loading
  • Transformer Rating Verification
  • Thermal Model Calibration and Recalibration
  • Protect against Overloading
  • Available with Up to 8 Channels

The ThermAsset®2 is a much sought after addition to LumaSense's Luxtron product line, offering a primary controller to monitor hot spots, control cooling, and protection at a cost that is attractive to the apparatus engineers and system operators. Now available in your choice of 2, 4, 6, or 8 channel configurations, the ThermAsset2 offers full control with alarm status indicators for up to six customer-specific relay functions.

This controller offers many of the reliable and proven features, considered the standard for fiber optic temperature measurement of transformer windings in the Power Utility industry. The same-patented Fluoroptic® Thermometer (FOT) technology is employed using a lifetime LED light source to activate the sensors. The ThermAsset2 utilizes the LumaSense ruggedized probes, the toughest in the industry, which require no calibration over the life time of the transformer. The ThermAsset2 meets 3000V surge protection requirement (IEEE C37.90.1- 1989).

Small and medium size transformers often take the brunt of the load in an overload condition and thus are most likely to be damaged without proper control. It is well known and accepted, that winding hot spot temperature measurements are the only safe means to activate the cooling systems (fan and pumps) to provide transformer thermal protection from insulation damage. Conventional winding temperature indicators only 'infer' the hot spot by measuring top oil temperature. The ThermAsset2 enables direct, real time, accurate measurement of transformer winding temperature thereby providing valuable input to calibrate thermal models and enable dynamic load control. The drift-free, calibration-free nature inherent in the Fluoroptic® technology makes these systems ideally suited for use in transformers and provides a cost effective and reliable means to help protect these valuable assets.

LumaSense's 'ruggedized' probes, have become the industry standard for fiber optic probe construction for use in transformers. Based on the company's patented Fluoroptic technology, which is immune to EMI and high voltages, these probes are inherently safe, reliable and stable, and are built from materials designed to survive the life of a power transformer.

LumaSense Applications Engineers are available to work with OEMs and Utilities to facilitate the setup and integration of the company's ThermAsset®2 control system.

  • Number of Channels : 2, 4, 6, or 8
  • Measurement Range : -30 to +200° C
  • Accuracy : ±2° C
  • Analog Output : 0-1mA or 4-20mA (Optional)
  • Digital Communication : RS-232 and RS-485 available
  • Operating Environment : -40 to 70° C
  • Power : Universal AC and DC (90-265 VAC/DC)

  • Number of Channels  : 2,4,6 or 8
  • Temperature Range :  -30°C to 200°C
  • Accuracy : ±2°C
  • Front Panel Display  : Large 1' LED for Each Channel
  • Probe Signal Strength Readout : Single Push Button Accessible for All Channels
  • Input Power : Universal AC/DC [90-265VAC/DC]
  • Analog Output : 4-20mA or 0-1 mA
  • Serial Output : RS-232 and RS-485
  • Number of Relays : 6 Form-C Programmable Cooling Control and Alarm Setpoints either Factory Programmed or via RS232 and RS482 from Computer
  • Self Diagnostic : Self Diagnostic and probe errors available on front panel and RS-232
  • Temperature Data Storage  : Retains 300 days of data at 1 minute intervals on all channels and maximum temperature for each Channel Retained until Reset by User
  • LED Alarm indicators  : One for Each Relay
  • System Fault Relay  : 1 Form-C Relay
  • System Fault Status Indicator  : 2 LED's (Green=OK, Red=Faulty Condition)
  • Surge Protection : 3000V (IEEE C37.90.1-1989)
  • Connectors : All Ring-Lug Terminals
  • Operating Temperature range  : -40°C to +70°C
  • Storage Temperature : -30°C to +75°C
  • Probes  : Accepts all Luxtron Quality and DipTip Rugged ProbesTM
  • Communications : Modbus and DNP3 options available

Customer reviews

No reviews were found for ThermAsset - Model 2 - Effective Fiber Optic Hot Spot Monitor and Controller for Power Transformers. Be the first to review!