Model DMG - Double Membrane Biogas Holder
From Biogas Storage
Each store is individually calculated in terms of ...
Each store is individually calculated in terms of the loads (internal pressure, wind and snow loads). As a result, membranes are selected with high tensile strength. The PVC-coated membranes are hardly combustible according to DIN 4102 B1, fungicidal treatment and equipped with a UV protection. To protect the membranes from the substances contained in the biogas (CH4, CO2, H2S, etc.), the interior and bottom membranes on a special coating.
The supporting air blower provides the necessary pressure of the gas reservoir to absorb the external forces such as snow and wind load and to generate the form on the gas system. A separate air hose connects the fan to the memory.The check valve prevents air leakage in case of failure of the blower. For safety, a pressure control valve is installed in the air system. This valve controls the operating pressure and closes automatically at a minimum required pressure (static stability, failure of the fan) in the outer membrane. By this device, the memory remains stable at existing gas production. The level measurement enables an optimum utilization of the storage volume and control of the slave devices (eg torch, motor, burner, etc.).
- Double membrane gas tank for storage of sewage gas and biogas by ÖWAV rule sheet 30
- Cost-effective storage solution to 12.000m³ gas storage volume
- Ultrasonic level measurement
- With poor maintenance and support Energieefizienten air blowers
- With hydraulic high and low pressure protection
- Short installation time
- Optional Stand by supporting air blower
- Optional with gas detection system
- Optional Vorschachtausrüstung
Design Parameters
- Container sizes from 10 to 12.000m³
- Operating pressure about 5-50 mbar
- Ambient temperature -30 ° C to + 50 ° C
- Max. Permissible gas temperature + 50 ° C
- Max. Permissible operating pressure + 50 mbar
- Max. Allowable operating vacuum -2,5mbar
- Max. Permissible roof snow load 150kg / m²
- Max. Allowable wind load 150km / h - more snow and wind loads on request!