- Home
- Companies
- Enetics, Inc.
- Products
- Model LM-1312 - Board Set Power ...
Model LM-1312 -Board Set Power Analyzer/Recorder
The LM-5300 series comprises two unique 3-phase 600v board configurations and three embedded software packages (Models LM-5310/15 and LM-5320) each capable of simultaneously recording 4 voltages, 4 currents with events and power consumption. The 5315 and 5320 add harmonic and waveform capture capability. The fourth voltage and current channels allow neutral-ground voltage and neutral or ground current to be recorded. The emphasis is on meeting practical power monitoring needs for volume Original Equipment Manufacturers that have their own existing packaging platform. Please contact Enetics for complete details. Monitoring and analysis capabilities track those of Enetics` own line of recorder / analyzers.
- Board Set for high-volume OEMs
- Three Phase 600v Monitor / Recorder
- Power Quality + Power Consumption
- Modem/Paging Options
- Self-Powered Dual Range Flexible SMART CT’s
- Pre-programmed
- 3 Year Warranty
Software
The LM-5300 series is compatible with Enetics PowerScape (LMS-5700) software which consists of two major components, the database (SQL) and the charting/reporting software. The database automatically aggregates data collected from one or more designated sites. Data is easily retrieved to generate the required charts and reports. For user flexibility and extensibility, charts and reports are generated in Microsoft Excel. The Excel worksheet data file can then be exported in various formats and shared among users. Zooming and panning is available on the charts. A key advantage of using an SQL database and Excel is that it is an “open” system, you are not locked into any suppliers’ proprietary software. You can retrieve any data available from the database and/or use the Excel data to generate additional charts and reports.
Channels:
- Voltage- 4 (single-ended)
- Current- 4 (Simultaneous current and voltage sampling)
Range:
- Voltage- 20-600vac
- Current- CT Dependent (10ma-10,000A)
Memory:
- Non-volatile 4MB.
Sample Rate/Response Time:
- 32 samples/cycle for interval data
- 128 samples/cycle for harmonic analysis
Accuracy:
- Voltage- 0.2% reading + 0.1% FS
- Current- 0.2% reading + 0.2% FS
- Power- 0.5% reading + 0.01% FS
- Power Factor - + 1%
- THD - + 1%
Response Time/Recording Interval
- Response Time: 1 cycle
- Recording Interval: 15 sec to 1 hour (Wraparound)
- Typical Recording Time:
- 15 Min Interv/16 Parameters- 100 Days min
- 15 Min Interv/117 Parameters- 600 Days min
- Software reports available recording duration at setup.Waveform and event capture storage is independent of interval data storage.
- 3000 Sag/Swell events can be stored in non-volatile memory
Harmonics:
- Up to 25th
Communications:
- Internal Modem Data Rate: 2.4 kbps
- Serial Port: 57.6 kbps
Power:
- 120/240vac, 50/60Hz
- Run-through time: 10 sec
Environmental/Physical:
- Operating Temp Range: -20ºC to +70ºC
- Size: 8.5” x 7” x 2.7” (21.6 x 17.8 x 6.8 cm) Non-conductive Case
- Weight: 3.5 lbs (1.6 kg)