Sonel S.A.
  1. Companies
  2. Sonel S.A.
  3. Products
  4. Model MZC-306 - Loop Impedance Meter

Model MZC-306 -Loop Impedance Meter

SHARE
Loop impedance measurement with resolution 0,01 Ω. Loop impedance measurement without tripping the circuit breaker > 30 mA with resolution 0,01 Ω (100...440 V). Measurements possible in installations 110/190 V, 115/200 V, 127/220 V, 220/380 V, 230/400 V, 240/415 V, 290/500 V and 400/690 V (range 100...750 V). Short circuit current indication. Voltage measurement up to 750 V and up to 250 V with resolution 0,1 V. Measurements using Uni-Schuko adapter or test wires 1,2; 5; 10 and 20 m. Memory of 990 records. USB connection with PC
Powered by disposable or rechargeable (4xLR14).
Most popular related searches

Measurement of short circuit loop impedance (ZL-PE, ZL-N, ZL-L)
Measuring range according to IEC61557: 0,13…1999 Ω for 1,2 m test leads; 0,25…1999 Ω for UNI-SCHUKO adapter

  • rated operating voltage UnL-N/ UnL-L: 110/190 V, 115/200 V, 127/220 V, 220/380 V, 230/400 V, 240/415 V, 290/500 V, 400/690 V,
  • operating voltage range: 100…440 V (for ZL-PE and ZL-N) and 100…750 V (for ZL-L)
  • high current measurement (up to 30 A),
  • operating frequency range: 45…65 Hz,
  • control of correctness of PE terminal connection by means of a contact electrode (applicable to ZL-PE),
  • measurement is also possible when L and N circuits are swapped,
  • measurement of resistance and reactance components,
  • short circuit current calculation.

Measurement of short circuit loop impedance ZL-PE RCD (without RCD tripping)
Measuring range according to IEC61557: 0,43...1999 Ω for 1,2 m test leads; 0,50...1999 Ω for UNI-SCHUKO adapter

  • operating voltage range: 100 ... 440 V,
  • rated operating voltage Un: 110 V, 115 V, 127 V, 220 V, 230 V, 240 V, 390 V, 400 V,
  • control of correctness of PE terminal connection by means of a contact electrode,
  • measurement is also possible when L and N circuits are swapped,
  • measurement of resistance and reactance components,
  • short circuit current calculation.

Voltage measurement

  • frequency range 45…65 Hz,
  • overvoltage alarm.

Electrical safety:

  • type of insulation: double, according to IEC 61010 - 1
  • measurement category: CAT IV 600 V (CAT III 1000 V)
  • protection class acc. to EN 60529: IP54

Other technical data

  • power supply: alkaline batteries or NiMH rechargeable batteries, LR14 (4 pcs)
  • number of Z measurements (for alkaline batteries): > 5000
  • time to Auto-OFF: 300 seconds
  • data transmission: USB
  • memory of measurement results: 990 cells, 3500 entries
  • display: LCD segment
  • dimensions: 288 x 223 x 75 mm
  • meter weight: ca. 2 kg

„m.v.” measured value