Huazheng Electric Manufacturing (Baoding) Co.,Ltd.
  1. Companies
  2. Huazheng Electric Manufacturing ...
  3. Products
  4. Huazheng - Model HZZL-3 ASTM D971 - ...

HuazhengModel HZZL-3 ASTM D971 -Transformer Oil Interfacial Tension Meter

SHARE

The HZZL-3 ASTM D971 Transformer Oil Interfacial Tension Meter is a simple and easy to use testing instrument that uses physical methods instead of chemical methods.

Most popular related searches

The ASTM D971 Transformer Oil Interfacial Tension Meter is a simple and easy to use testing instrument that uses physical methods instead of chemical methods. The amount of intermolecular tension reflects the physicochemical properties of the liquid sample and is one of the important indicators of product quality. And our ASTM D971 Transformer Oil Interfacial Tension Meter with automatic interfacial tension meter can quickly and accurately measure the surface and interfacial tension values of various liquids, and display the results automatically.

Our ASTM D971 Transformer Oil Interfacial Tension Meter has won the favor of users in the market with its good performance and reasonable price. It adopts electromagnetic force balance type sensor to improve the measurement accuracy, and it is very convenient to adjust the instrument by calibrating one point. It is integrated temperature detection circuit, which automatically compensates the temperature for the test results. The instrument has RS232 interface device, which can be connected with computer to facilitate data processing.

Measuring Range: 0-200mN/m
Accuracy: 0.1%( test result)±0.1 mN/m
Precision: 0.1mN/m
Sensibility: 0.1mN/m
Mains Voltage: AC220V±20%, 50HZ±10%
Maximum Power Dissipation: 20W
Suit Ambient Temperature: 10~30?(25?the best)

1. Working environment:
The working environment of the instrument should meet the requirements mentioned in Chapter 4.

2. Platinum ring:
The plane of the ring should be parallel to the page on the north side, and the ring should have a certain roundness. The platinum ring should be clean, and it can be cleaned with detergent, and then rinsed with pure water, and then the platinum wire is heated in the oxidation flame of the alcohol lamp to orange-red.

3. Test cup:
The test cup should be clean, and it can be cleaned and washed, then rinsed with hot water, and finally rinsed with pure water, and drained before use.

4. Obtaining pure water:
It is best to use distilled water that has been purified multiple times. Tests have shown that some commercially available purified drinking water can meet the experimental requirements.

5. Calibration of the instrument:
After the instrument is subjected to a large impact, or after moving, the weight in the setting items should be calibrated.