LAMTEC America Inc.
  1. Companies
  2. LAMTEC America Inc.
  3. Products
  4. LAMTEC - Model F300K - Flame Scanners

LAMTECModel F300K -Flame Scanners

SHARE

Flame scanners that comply out of the box with NFPA 85 proof-of-flame requirements, that easily retrofit to existing mount tubes, that wire into existing BMS or other safety control systems with only 4 connections needed, means shortened conversion time, lower install cost. And with ruggedized in-unit electronics, the entire installation and commissioning is done simply at the point of physical connection to the burner saving even more time and money.

Most popular related searches
  • 3 operating modes
  • 14 frequency ranges
  • Available as single or double sensor (IR/UV)
  • Degree of protection IP67
  • Flame ON/OFF self-learning function
  • Operation via graphic User Interface with status display (optional)
  • SIL 3 according to DIN EN 61508 part 1-7
  • Available with Class I, Division 2, Group A, B, C, D, Hazardous Locations
  • Supply voltage : 24 VDC ± 20 % ≤ 3,5 W
  • Flame and fault contact :
  • ≤ 50 VDC, ≥ 6 VDC
  • ≤ 0,5 A, ≥ 1,0 mA floating
  • Frequency range : 10 / ... / 110 ... 210 Hz 7 levels in the standard version
  • Safety time "Operation" : t ≤ 1 sec. (standard) t ≤ 1, 2, 3, 4, 5 sec. (selectable via password)
  • Operating mode : Continuous operation
  • Degree of protection : IP67 NEMA 4X
  • Operation temperature : -40 °C ... + 85 °C
  • Dimensions (HxT) : 99x195,5 mm
  • Weight : 1,05 kg (aluminium) 3,6 kg (stainless steel)
  • Material :  Corrosion-resistant aluminium EN AW 6082 (seawater 2*; atmospheric condition 1*), anodised or stainless steel
  • * Comparative evaluation from 1 (very good) to 6 (unsuitable)