Pelltech EvercleanModel PK 50 -Pellet Boiler

SHARE

Pelltech boilers serve a highly effective and convenient solution for heating systems in single and semi-detached houses as well as smaller public buildings. Easy integration with Pelltech PV-series burners ensures efficient, environmental and cost effective pellet combustion. All Pelltech boilers are equipped with the new Smart House controller which can control up to two weather compensated hydronic circuit actuators and pumps. It is able to manage up to seven temperature sensors, an oxygen sensor, internet module and wireless sensors.

Most popular related searches
  • Vertical 2-pass boiler with large water content
  • Automatic heat exchanger cleaning with rotating turbulators
  • Big built in ash container
  • Integrated Smart house controller for burner, boiler and house control
  • Boiler internet connection allows remote control, data logging and firmware updating
  • Fluegas and water outlets can be directed either to the top or back
  • Huge ash container

    Big (54 l ) built in ash container needs emptying approximately once a month

  • Draught control

    Integrated flue gas fan working by draught sensor

  • Safety thermostat

    prevents water from exceeding 95 C

  • Fully automatic cleaning process

    This boiler cleans itself, the only need is to empty the ash container about once a month

  • Safety valve

    is activated when pressure in the boiler reaches 2.5 bar

  • Safety door switch

    prevents burner from starting up when door is open. If the door is opened during burning process, the switch triggers burner to stop. Burning process will automatically resume once the door is closed again.

  • Rated thermal output kW 47
  • Boiler class according to EN 303-5  5
  • Efficiency at 70 °C % 94
  • Minimal returning water temp. °C 55
  • Recommended working temp. °C 75
  • Highest working temp. °C 90
  • Safety thermostat triggering temp. °C 95
  • Flue gas temperature at rated output °C 150...180
  • Permissible operative pressure bar 2.5
  • Test pressure bar  4
  • Boiler water volume l 150
  • Ash container volume l 54
  • Boiler weight kg 313
  • Boiler dimensions (L/W/H) mm 600/800/1510
  • Intake width without side panels mm 500
  • Combustion chamber dimensions (L/W/H) mm 330/600/700
  • Mains supply  230V, 50Hz
  • Electrical consumption at ignition W 500
  • Electrical consumption during work W 50
  • Electrical consumption at standby W 3
  • Electrical heating element kW 9
  • Combustion air inlet hatch cm² ≥300
  • Burner`s fixing flange mm 90
  • Required chimney diameter mm ≥120
  • Flue gas outlet ⌀ mm 112
  • Boiler back connections pcs 2xRp1"
  • Boiler top connections  pcs 2xG1"
  • Distance between top connections mm 125
  • Number of turbulators pcs 7
  • Required safety valve connections pcs 1xDN20