Cleaver-Brooks
  1. Companies
  2. Cleaver-Brooks
  3. Products
  4. Cleaver Brooks - Model FLX - Watertube ...

Cleaver BrooksModel FLX -Watertube Boiler

SHARE

The FLX boiler package includes a burner, trim, and control system for a completely integrated and engineered solution from a single source. Each boiler design was witness tested by a third party in Cleaver-Brooks state of the are boiler laboratory to ensure maximum reliability. FLX has distinct design features that include non-welded ferrule tubes for ease of tube replacement; removable sectioned side panels permit full access to all tubes. FLX boilers are a 5-pass cross flow water tube design, optimized through computational fluid dynamics to maximize heat transfer thru every pass. Unlike competing designs, FLX features a water-cooled furnace and fireside passes that do not require baffles, which lowers refractory maintenance costs throughout the boiler’s life and reduces the total cost of ownership.

Most popular related searches
  • Up to 15:1 turndown (Standard emissions) and 10:1 (Controlled emissions)
  • Rapid response to swinging loads
  • Small footprint, field erectable
  • Thermal shock resistance, 25-year limited pressure vessel warranty
  • Reliable burner, 10-year limited burner warranty
  • Easy burner and pressure vessel access for service and maintenance

FLX field erectable option allows for boiler replacement in tough-to-access spaces. The pressure vessel is assembled at the factory and hydro-tested before shipment. During the disassembly, the tubes are matched marked for easy installation on site.

  • Steam or Hot Water
  • 1,500-25,000 MBH Input
  • Natural Gas, #2 Light Oil, Propane, Digester Gas
  • 15-250 psig Design Pressure
  • Available to <9 ppm NOx
  • Field Erectable

The FLX is a UL listed packaged boiler that is versatile and can handle both commercial and Industrial applications. The compact 5-pass bent water-tube design provides efficiency ratings up to 81% (Steam) and 85% (Hot water).

The FLX's burner can burn non-standard and renewable fuels and features a fully modulating burner to ensure optimum efficiency throughout the firing range. It can also help meet emissions reduction goals, down to <9 ppm NOx with low CO.

  • Process Steam
  • Industrial Process
  • Building Heat
  • Sterilization
  • Healthcare
  • Boiler Horsepower: 36 - 600
  • Emissions (ppm NOx) : Standard, <30, <20, <9
  • Fuel: Natural Gas, #2 Oil, Propane, Digester Gas, Combination Firing
  • Input Capacity (MBH) : 1,500 - 25,000
  • Number of Passes: 5
  • Steam or Hot Water: Both